3 Piping work and refrigerant charge
Refrigerant piping range
SMGB0091 rev.2 - 11/2015
46
Line branch installation
A
A
B
(mm)
Multi-kit model A
Multi-kit model B
RASC unit
Pipe Size (L0,x1,x2)
Gas
Liquid
(4-6) HP
Ø15.88
Ø9.52
E-102SN3
E-102SN3
8 HP
Ø25.4
Ø9.52 (*)
E-162SN3
E-102SN3
10 HP
Ø25.4
Ø12.7
E-162SN3
E-102SN3
(*): In case that pipe length between RASC unit and the farthest indoor unit exceeds 70m in 8 HP, please use a Ø12.7 pipe as a liquid
pipe.
(mm)
Indoor unit capacity
Pipe Size (L3)
Gas
Liquid
(0.8-1.5) HP
Ø12.7
Ø6.35
(1.8/2.0) HP
Ø15.88
Ø6.35
(2.3-6.0) HP
Ø15.88
Ø9.52
8.0 HP
Ø19.05
Ø9.52
10.0 HP (*)
Ø22.20
Ø9.52
?
N O T E
(*): In combinations with 10.0HP indoor units, only one of the two connections of the E-102SN3 multi-kit admits the Ø22.20 mm diameter
corresponding to the gas pipe of the 10.0HP indoor unit. Please take this restriction into account in case that the installation requires the
connection of gas piping of 10.0HP indoor units.