10 Troubleshooting
Troubleshooting procedure
SMGB0091 rev.2 - 11/2015
205
10
Alarm code
03
Abnormal transmission between the indoor units and the RASC unit
• This alarm is displayed when abnormal operation is maintained for three minutes after normal transmission has been
confirmed between the indoor units and the RASC unit. Also, when abnormal operation continues for 30 seconds
after the micro-computer is automatically reset.
• The alarm is displayed when the abnormal transmission is maintained for 30 seconds from the starting of the RASC
unit.
• Investigate the cause of the overcurrent and take the necessary action when the fuses are blown out or the circuit
breaker for the RASC unit is activated.
• This alarm code may be indicated when the inverter PCB and the RASC unit cannot secure the power source (No
indication on the 7-segment of RASC unit PCB). In this case, make sure to check the inverter PCB and the continuity
of the fuse on the circuit.
(Refer to the next page)