6 Optional functions
Optional functions
SMGB0091 rev.2 - 11/2015
109
6
6.2.2
Optional functions through remote control switch
In addition to the possible optional functions through the 7-segment display of the RASC unit’s PCB and through DIP
switch setting, there are available a large quantity of optional functions for each remote control switch connected to the
system.
An example of the available optional functions through the HITACHI individual remote controls (PC-ARF/PC-ART) is
shown below:
?
N O T E
For the detailed information about optional functions through remote controls, please refer to the Technical catalogue of Packaged
controllers.
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
b1
Removal of heating
temperature
compensation
O
00
Standard setting.
It increase the
tempe4ºC
This function is used when the temperature
setting displayed on the remote control
switch and the inlet air temperature of the
indoor unit must be the same.
01
Removal
02 (*1)
It increase the
tempe2ºC
b2
Circulator function at
heating Thermo-OFF
O
00
Not activated function
This function means that the fan unit
remains running at the same speed during
Thermo-OFF condition to prevent the air in
the room from stratifying.
01
Activated function
b3
Forced compressor
operation for at least
3 minutes
O
00
Not activated function
This function is used to protect the
compressor, preventing it from being
started or stopped for periods of less than
three minutes.
01
Activated function
b4
Pre-determined
filter cleaning period
change
O
00
Standard (1200 h
factory setting) (*2)
This function is used to modify the period
until the next display of filter cleaning sign.
01
100 hours
02
1200 hours
03
2500 hours
04
No indication
b5
Fixing of operation
mode
X
00
Not activated function
Once the unit operating mode has been
selected, this function prevents it from
being modified from the remote control.
01
Activated function
b6
Fixing of setting
temperature
X
00
Not activated function
Once the unit temperature has been
selected, this function prevents it from
being modified from the remote control.
01
Activated function
b7
Fixing of cooling
operation
X
00
Not activated function
This function is available to use cooling
mode only and to prevent heating mode
from being enabled.
01
Activated function
b8
Automatic COOL/
HEAT operation
X
00
Not activated function
This function allows the automatic change
from the cooling to the heating mode for
the units with the same refrigerant cycle.
01
Activated function
b9
Fixing of indoor unit
fan speed
X
00
Not activated function
Once the indoor unit fan speed has been
selected, this function prevents it from
being modified from the remote control.
01
Activated function
bA
Not available
X
“- -”
permanent
Not available
–