10 Troubleshooting
Troubleshooting procedure
SMGB0091 rev.2 - 11/2015
207
10
RASC-(8/10)HNPE
Is DSW5-1P (Terminating
resistance) on RU PCB1
ON?
Set it correctly
RU: RASC unit
IU: Indoor unit
Check power source for
RASC unit (ELB, etc.)
(AC power is not coming to the PCB)
(AC power is not coming to the PCB)
Is LED4 (red) RASC
RU PCB1 ON?
Is LED3 (yellow) on
R.U. PCB1 ON?
Is LED3 (yellow) on IU
PCB ON?
Is LED3 (yellow) ON even
if connector “CN2” of IU
PCB is removed?
Does alarm occur with
all indoor units?
Failure of RU PCB
Failure of IU PCB
Check other indoor
units
Check wiring between
RU and IU or fuse for
IU PCB and PCB1.
Replace fuse if failed
Is LED3 (yellow) on IU
PCB flashing more than
once in 10 seconds
Does refrigerant system
Number setting between
RU and IU correspond?
(RU:DSW4 and RSW1) (IU:
DSW5 and RSW2) *4)
Is LED3 (yellow) on
RU PCB1 flashing
more than once in 10
seconds?
Reconnect connector
“CN8” (red) of RU PCB1
Is IU PCB setting Non-pole
operating *2)
Set it correctly
Set it correctly
Failure of IU PCB
RPK-FSN(H)3M, RPC-FSN3, RCIM-FSN3, RCI-FSN3 only
Remove connector
“CN8” (red) of PCB1 (*1)
Is there 400V between
phases L1/L2/L3 of the
terminal board?
Is there 400V between
phases L1/L2/L3 of the
terminal board?
Check if CB1, CB2, R1,
R2, RS1, RS2 are correct
Is there 230V between
1-3 of PCN202 of PCB2?
Is the fuse EFR1 on
RASC PCB2 blown
out?
Faulty RASC PCB2
Faulty RASC PCB2
Faulty RASC PCB4
Replace the faulty
component
Faulty RASC PCB1
Failure of PCB1 *5)
Control (Abnormality of the
microcontroller, power source (secondary
side), circuit for transmission)
Indoor
unit
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes (Correct)
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
(Failure)
Is LED201 (red) on
PCB4 ON?
Is LED1 (red) on
RU PCB1 ON?
Check power source for
RASC unit (ELB, etc.)