4.2 System wiring diagram
Connect the units (RASC and indoor unit) according to the following electric diagram:
• Connect the operation wiring to the units in the same refrigerant cycle (The refrigerant piping and the control wiring
should be connected to the same indoor units). If the refrigerant piping and the control wiring are connected to the
units in the different refrigerant cycle, it may cause a abnormal operation.
•
Use twist pair wire (more than 0.75 mm²) for operation wiring between RASC unit and indoor unit, and operation
wiring between indoor units (H-Link connection). It can be also used shielded pair wiring. Shield shall be connected to
earth only in one cable side.
• Use shielded wires for intermediate wiring to protect the units from noise obstacle at length of less than 300 m and
size complied with local code.
• Do not use more than 3 cores for operation wiring (H-Link). Core sizes must be selected according to the national
regulations.
• Open a hole near the connection hole of power source wiring when multiple RASC units are connected from one
power source line.
•
The recommended breaker sizes are shown in Table of electrical data and recommended Wiring, Breaker Size/1
RASC unit.
•
In the case that a conduit tube for field-wiring is not used, fix rubber bushes with adhesive on the panel.
!
C A U T I O N
•
All the field wiring and electrical components must comply with local codes.
• Pay attention to the connection of the operating line. Incorrect connection may cause the failure of PCB.
3 N
3 N
Terminal board
Circuit breaker
Earth leakage breaker
Field wiring
Field-supplied
Optional accessory
Power source from the RASC
unit to the indoor unit
Independent power source of RASC
unit and indoor unit (example)
Operating line (twisted
shielded pair cable or shielded
pair cable)
DC5V (non-pole transmission,
H-LINK system)
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Operating line (twisted
shielded pair cable or
shielded pair cable)
DC5V (non-pole
transmission, H-LINK
system)
Remote control switch
(example for simultaneous control)
Remote control switch
(example for simultaneous control)
RASC unit of
system number 0
RASC unit of
system number 0
4 Electrical and control settings
System wiring diagram
SMGB0091 rev.2 - 11/2015