5 Control system
Standard operation sequence
SMGB0091 rev.2 - 11/2015
82
5.3.2 Dry operation
Temperature
on the top of
compressor
Power to
R.U: ON
Power to CH: ON
Power to CH: OFF
I.U:
Indoor unit
R.U:
RASC unit
> 80 ºC
Power to I.U:
ON
Power to PCB in
I.U: ON
Start of transmission between I.U
and R.U
Start of transmission between I.U
and remote control switch
Auto-louver 0
Reset
Power to YH2 in
I.U: OFF
FS
MD: ON
< 75 ºC
OFF
(Higher than activation level)
ON
(Lower than activation level)
(for unit with drain pump)
Setting at
DRY
DRY indication
Set temperature
indicated
Pressing
TEMP switch
Switch: increasing set temperature
Switch: decreasing set temperature
Pressing
RUN/STOP
switch
Run LED: ON,
RUN is indicated
Power to YH2 : ON
MD: ON
(for unit with drain pump)
IU Fan Operation:
Low
IU
air intake
temp.
DRY
operation
Power to MC: OFF
Power to MIF: OFF
6 min.
IU fan
operation: low
to 1
Higher than set
tempe2 ºC
Lower than set
temperature
< -5 ºC
≥ -5 ºC
No
Yes
Power to
Y52C : ON
6
min.
No
Yes
1
sec.
Outdoor
Temperature
No
Yes
Power to
MC
Power to YH2 in
I.U: ON
RASC Fan MOF operation
(Only for indoor unit with
auto-louver)