10 Troubleshooting
Troubleshooting procedure
SMGB0091 rev.2 - 11/2015
230
Alarm code
31
Incorrect capacity setting or combined capacity between indoor units and RASC unit
•
This alarm code is indicated when the undefined setting is set to DSW3 on the RASC unit PCB.
• This alarm code is indicated when the total indoor unit capacity is outside the range allowed of the combined RASC
unit capacity.
• RASC unit capacity setting is not correct.
Is DSW3 on the outdoor unit
PCB1 set correctly?
Set the capacity for PCB1
No
Yes
Is DSW3 on the indoor unit PCB
set correctly?
Set the capacity for PCB
No
Yes
Total capacity of the indoor
unit(s) is wrong
Phenomenon
Cause
Check item
Action
(Turn OFF Main Switch)
Incorrect Capacity Setting of Indoor Unit
Check combination of indoor
units and capacity setting on
PCB.
Correctly set dip switch, DSW3.
Incorrect Capacity Setting of RASC unit
Check capacity setting on
RASC unit PCB.
Correctly set dip switch, DSW3.
Total Indoor Unit Capacity Connected to the RASC unit is Beyond
Permissible Range
Check RASC unit model by
calculating total indoor units
capacity.
Ensure that total indoor unit
capacity is within 75~120%
?
N O T E
• In case of H-LINK system, this alarm code is indicated when DSW4, RSW1 (for refrigerant system setting) on the RASC unit PCB and
DSW5, RSW2 (for refrigerant system setting) on the indoor unit PCB are incorrectly set.
• In this case, set correctly DSW4, RSW1, DSW5 and RSW2 after turning OFF main switch.
• (RSW2 is not equipped with some models.)