10 Troubleshooting
Troubleshooting in check mode
SMGB0091 rev.2 - 11/2015
260
(9) No Function
This function is not used.
Press “OK” to proceed.
0 7 : 0 0 0
Self Checking
07: No function
08: Transmission test
(10) Transmission Circuit Test
The remote control switch automatically starts to check the transmission circuit.
(11) Remote Control Switch Thermistor Test
The temperature detected by remote control switch thermistor is displayed at
“ A
” in the right figure.
0 9 : 0 2 5
Self Checking
(12) Date/Time Test
The date and time is switched from “2012.03.04 12:34” to “2008. 01. 01 00:00”.
1 0 : 0 0 0
2008.01.01 00:00
Self Checking
(13) EEPROM Test
< EEPROM Clearing Cancel >
Press “?“ (help).
< EEPROM Clear >
Press “OK” or wait 15 seconds. EEPROM data will be cleared. During the
process, the numbers will be indicated on where “ A ” is located.
If A indicates “999”, EEPROM is in a faulty condition.
* In case “ A ” indicates “999”, the process does not proceed to next step.
11 : 0 0 0
Self Checking
(14) After the several seconds pass, the self checking is completed and the remote control switch automatically restarts.
EEPROM process
(15) Clear EEPROM
The remote control switch will automatically start EEPROM clearing process.
1 3 : 0 0 0
Self Checking
(16) After the several seconds pass, the self checking is completed and the remote control switch automatically restarts.