10 Troubleshooting
Troubleshooting procedure
SMGB0091 rev.2 - 11/2015
213
10
Alarm code
06
Excessively low voltage or excessively high voltage for the inverter PCB
This alarm code is displayed when the voltage of DIP-IPM is insufficient or excessive and the alarm has three
occurrences in 30 minutes. If the number of occurrences is smaller than two, the retry operation is performed.
RASC-(4-6)HNPE
No
Check wiring and
cable capacity
Frequency can
increase higher than
60 Hz
Restart the operation
Faulty DIP-IPM.
Replace it. (*)
Connect correctly
Yes
Yes
No
Yes
No
Yes
Compressor stops
immediately
(lower than 20 Hz)
Compressor stops
when frequency
increase. (Approx.
20 Hz to 60 Hz)
Fault magnetic
contactor. Replace it.
No
No
Is the power
supply voltage
400V±10%?
Does the
voltage fall during
operation by operation of
other apparatus?
Is LED201 on
DIP-IPM ON after
magnetic contactor for
compressor (CMC) is
turned ON?
How is
compressor
operation?
Is connection
correctly between DIP-
IPM, reactor (DCL) and
CMC?
Is the power
supply voltage 323V
during operation?
Is the
magnetic contactor
for compressor (CMC)
function properly?
No
Yes
Faulty DIP-IPM.
Replace it. (*)
Check the wiring of
DIP-IPM. If wiring is
correct, faulty DIP-
IPM. Replace it. (*)
Yes
*Be careful especially because of high voltage
DIP-IPM: Inverter PCB of RASC unit.
?
N O T E
(*): Regarding replacing or checking method for the DIP-IPM, refer to the paragraph
in section