10 Troubleshooting
Troubleshooting procedure
SMGB0091 rev.2 - 11/2015
210
Alarm code
04
Abnormal transmission between Inverter PCB and RASC PCB1
This alarm is displayed when the abnormal operation is maintained for 30 seconds after the normal transmission
between the control PCB and the inverter PCB on RASC unit. Also, the abnormal operation is maintained for 30 seconds
after the micro-computer is automatically reset. The alarm is displayed when the abnormal transmission is maintained for
30 seconds from the starting of the RASC unit.
RASC-(4-6)HNPE
Replace fuse if blown
Faulty PCB1
Power source OFF.
Power source ON.
Faulty DIP-IPM.
Faulty DIP-IPM.
Incorrect wiring.
Remove the connectors PCN201
and CN201 on DIP-IPM.
No
No
No
No (LED2 remains ON or OFF)
No (LED2 remains ON or OFF)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Remove the connector CN6 on
PCB1. Power source ON.
Connect the connector CN6 on
PCB1.
Normal DIP-IPM. Check the wiring
again.
Normal DIP-IPM. Check the wiring
again.
Are the fuse (EF1)
on PCB1 and power fuses
(EF1,EF2) normal?
Does flashing speed
become faster than before?
Does flashing speed
become faster than before?
Is LED2 (Green) on PCB1
flashing?
Is LED2 (Green) on PCB1
flashing?
Is LED2 (Green) on PCB1
flashing?
?
N O T E
Investigate the cause of fuse blown
No (LED2 remains ON or OFF)
Faulty DIP-IPM.
No
Yes
Is LED201 on DIP-IPM
ON?
PCB1: Control PCB in outdoor unit
DIP-IPM: Inverter PCB in outdoor unit