10 Troubleshooting
Checking procedure for main parts
SMGB0091 rev.2 - 11/2015
271
10
Checking method of resistance for inrush current prevention (Built-in thermal fuse)
(Measure the resistance under 1 kΩ range of a circuit tester.)
By placing the
+
side of tester to the
+
side of DM1
(soldering portion) on DIP-IPM and the
-
side of
tester to DCL1 DIP-IPM, measure the resistance. If the
resistance is around 500Ω, it is normal. If the resistance
is 0Ω or infinity Ω, it is abnormal.
Contact with specified
terminals to measure.
Tester
Checking method of fuse for DIP-IPM protection (EF331)
(Measure the resistance under 1 kΩ range of a circuit tester.)
By placing the
+
and
-
side of tester to EF331 on
DIP-IPM, measure the resistance.
If the resistance is 0Ω, it is normal.
EF331
Contact with specified
terminals to measure.
Tester