6 Optional functions
Optional functions
SMGB0091 rev.2 - 11/2015
114
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
Fb
Lock function
for swing louvre
operation
X
00
Not activated function
This function is used to prevent changes to
automatic louvre operations.
01
Activated function
(factory setting)
FC
Lower limit of setting
temperature for
cooling operation
X
00
Standard
This function is used to limit the lowest
setting temperature for FAN/COOL/DRY
modes.
01
Lower limit +1 ºC
02
Lower limit +2 ºC
03-08
Lower limit
+(03-08) ºC
09
Lower limit +9 ºC
10
Lower limit +10 ºC
Fd
Upper limit of setting
temperature for
heating operation
X
00
Standard
This function is used to limit the highest
setting temperature for HEAT mode.
(Settings 11 and 12 are not available for
PC-ART).
01
Lower limit -1 ºC
02
Lower limit -2 ºC
03-10
Lower limit
-(3~10) ºC
11
Lower limit -11 ºC
12
Lower limit -12 ºC
FE
Not available
–
00
Not available
–
01
(Used as 00 conditions)
02
FF
PC-ART: Lock
function for timer
X
00
Not activated function
This function is used to lock timer
activation.
01
Activated function
(factory setting)
PC-ARF: Not
available
–
00
Not available
–
01
(Used as 00 conditions)
H1
PC-ART:
Maintenance alarms
O
00
Display
This function is used to display or hide
maintenance alarms.
01
Hide
PC-ARF: Not
available
–
00
Not available
–
01
(Used as 00 conditions)
H2
PC-ART: Automatic
control indication
O
00
Display
This function is used to display or hide the
automatic control indication.
01
Hide
PC-ARF: Indication
of hot start
X
00
Display
This function is used to display or hide the
Hot start “HOT-ST” control indication.
01
Hide
H3
PC-ART: Operating
mode change
restriction
O
00
Operating mode
change disabled
(factory setting)
This function is used to configure
restrictions to the operation mode.
–
01
Operating mode set by
the central c
FAN mode
02
Unlimited operating
mode
PC-ARF: Not
available
–
00
Not available
–
01
(Used as 00 conditions)