6.1.2 Input and output signals through remote control switch
In addition to the external signals that can be selected through the 7-segment display on the RASC unit PCB, the remote
control switches provide extra input/output signals.
An example of the available external input and output signals through the HITACHI individual remote controls (PC-ARF/
PC-ART) is shown below:
Input and output number display and connectors
Input number display
Port
Factory setting
Input/Output indication
Setting item
Indication
Input 1
CN3 1-2
Remote ON/OFF 1 (Level)
03
Input 2
CN3 2-3
Prohibiting Remote Control after Manual Stoppage
06
Output 1
CN7 1-2
Operation
01
Output 2
CN7 1-3
Alarm
02
Output 3
CN8 1-2
Thermo-ON for Heating
06
Input and output settings and display codes
Indication
Input
Output
00
Not set
Not set
01
Room Thermostat (for Cooling)
Operation
02
Room Thermostat (for Heating)
Alarm
03
Remote ON/OFF 1 (Level)
Cooling
04
Remote ON/OFF 2 (Operation)
Thermo-ON for Cooling
05
Remote ON/OFF 2 (Stoppage)
Heating
06
Forbidding Remote Control after Manual Stoppage
Thermo-ON for Heating
07
Remote Cooling / Heating Change
Total Heat Exchanger
08
Elevating Grille Input
(not available for PC-ART)
Elevating Grille Output
?
N O T E
• After at least 3 minutes from the power ON, change the optional setting.
• The elevating grille input can be set to “Input 2” only. It cannot be set to “Input 1”.
• The elevating grille output can be set to “Output 1” or “Output 2” only. It cannot be set to “Output 3”.
• Do not set the elevating grille for the total heat exchanger.
• Record the setting conditions for each input and output in the “Setting” column of the table.
6 Optional functions
Optional external input and output signals