Description of the optional functions
Control of the indoor unit fan during Thermo-OFF in heating mode (
FA
)
The fan of the indoor units stops when the unit is in defrost operation. This function forces a start-and-stop cycle of the
indoor unit fan to prevent air stratification.
The start-and stop cycle operates as follows:
Fan motor operation
2 (min.)
Fan motor stoppage
6 (min.)
2 (min.)
6 (min.)
?
N O T E
When the indoor fans are stopped due to unit control, they remain stopped even if this function is enabled.
Night mode (Low noise) (
n
)
This function reduces the outdoor fan speed and the maximum compressor frequency value in cooling operation
according to the outdoor air temperature in order to reduce sound in low load conditions.
• Outdoor fan operation during this function:
22
25
60%
80%
110%
30
33
Maximum fan
speed percentage
(%)
Outdoor temperature (ºC)
?
N O T E
This function is only available in cooling operation for outdoor temperatures below 30ºC.
• Compressor operation during this function: The maximum limit of compressor frequency is lowered to approximately
50-60% of the maximum standard value.