4 Electrical and control settings
H-LINK II system
SMGB0091 rev.2 - 11/2015
71
4
4.7.4 DIP Switch setting for multiple H-LINK system
The DIP switches of all the RASC and indoor units have to be set as follows:
Unit
Name of DIP
switch
Mark
Setting before the
Shipment
Function
RASC unit
Terminal
resistance
DSW5
It is not necessary to set when the number of RASC
units in the same H-LINK line is one. In case of
more than one RASC unit in the same H-LINK line,
set as follows:
• First RASC unit: keep DSW5-1 in “ON”.
• Rest of RASC units: set DSW5-1 to “OFF”.
Refrigerant cycle
DSW4
RSW1
For setting the refrigerant cycle address of the
RASC unit. Set the DSW4 and RSW1 to overlap
the setting of other RASC units in the same H-LINK
system.
Indoor unit
Refrigerant cycle
DSW5
RSW2
For setting the refrigerant cycle address of
the indoor unit. Set the DSW5 and RSW2
corresponding to the address of RASC unit in the
same refrigerant cycle.
Address of the
indoor unit
DSW6
RSW1
Setting indoor unit address. Set the DSW6 and
RSW1 not to overlap the setting of other indoor
units in the same refrigerant cycle. (If no set, the
automatic address function is performed.)
• Example of the setting of the DIP switches.
RASC
units
Indoor
units
RSW1
Address of the indoor unit
(setting for the last digit)
DSW6
Address of the indoor unit
(setting for the tens digit)
RSW2
Number of refrigerant cycle
(setting for last digit)
DSW5
Number of refrigerant cycle.
(setting for tens digit)
RSW1
Number of refrigerant cycle
(setting for last digit)
DSW4
Number of refrigerant cycle.
(setting for tens digit)
DSW5
Terminal resistance
(00)
(01)
(02)
(00)
(00)
(00)
(00)
(01)
(01)
(02)
(02)
(02)
(00)
(01)
(02)
(03)
(00)
(01)
(00)
(01)
(02)