10 Troubleshooting
Troubleshooting in check mode
SMGB0091 rev.2 - 11/2015
247
10
Indication of micro-computer input/output
12 Micro-computer input/output in
indoor unit
C1
(a)
H2
52H
Y52C2
Y212
Y211
Y52C1
Y20B
Y20A
Heating Thermo-ON
Cooling Thermo-ON
(a)
(b)
Dark
Alarm
RASC fan
Dark
(Symbols with the letter Y are relays on the PCB)
13 Micro-computer input/output in
RASC unit
C2
-
(b)
Indication of unit stoppage cause
14 Cause of stoppage
d1
01
00
Operation OFF, Power OFF
?
N O T E 1
Explanation of term:
Thermo-ON: A condition that an indoor unit is requesting
compressor to operate.
Thermo-OFF: A condition that an indoor unit is not requesting
compressor to operate.
?
N O T E 2
Even if stoppage is caused by “Alarm”, “02” is not always
indicated.
?
N O T E 3
If transmission between the inverter printed circuit board and
the control printed circuit board is not performed during 30
seconds, the RASC unit is stopped.
In this case, stoppage is d1-05 cause and the alarm code
“04” may be indicated.
?
N O T E 4
If transmission between the indoor unit and the RASC unit
is not performed during 3 minutes, indoor units are stopped.
In this case, stoppage is d1-06 cause and the alarm code
“03” may be indicated.
01
Thermo-OFF, float switch activation (NOTE 1)
02
Alarm (NOTE 2)
03
Freeze protection, overheating protection
05
Instantaneous power failure at RASC unit (NOTE 3)
06
Instantaneous power failure at indoor unit (NOTE 4)
07
Stoppage of cooling operation due to low outdoor air
temperature
Stoppage of heating operation due to high outdoor air
temperature
10
Demand
13
Retry due to high pressure increase prevention
15
Vacuum/discharge gas temperature increase retry
16
Retry due to discharge gas superheat decrease
17
Retry stop due to inverter trip (Instantaneous over-current,
electronic thermal activation, current sensor abnormality)
18
Retry stop due to inverter trip (Voltage decrease, over-voltage,
transmission error, micro-controller reset, etc.)
19
Deviation of expansion valve opening
21
Forced Thermo-OFF
22
Outdoor hot start control
26
Retry due to high pressure decrease
28
Cooling air discharge temperature decrease
33
Forced Thermo-OFF
34
Forced Thermo-OFF
35
Retry due to abnormal operating mode
(Reversing valve switching failure)