6 Optional functions
Optional functions
SMGB0091 rev.2 - 11/2015
113
6
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
F0
Not available
-
-
Not used
–
F1
Automatic OFF timer
setting
X
00
Not activated function
This function is used to set the automatic
timer to switch off when the unit has been
started by remote control.
Do not set the functions "0C"-"0F" when
two remote control switches are used in
the same remote control group.
(Settings 0C, 0D, 0E and 0F are not
available for PC-ART).
01
1 hour
02
2 hours
03-24
(03-24) hours
0A
30 minutes
0B
90 minutes
0C
40 minutes
0D
45 minutes
0E
50 minutes
0F
55 minutes
F2
(*5)
Remote control
Master-Slave setting
X
00
Master
This function is used when two remote
controls are installed in a system. One of
them has to be set as “Master” and the
other one as “Slave”.
01
Slave
F3
(*6)
Automatic reset of
setting temperature
X
00
Not activated function
When this function is activated, once a
defined time (F4) has passed after the
last change in the setting temperature by
using the remote control switch, the setting
temperature returns to the selected cooling
(F5) or heating (F6) temperature values.
This function provides energy-saving.
01
Activated function
F4
Automatic reset time
X
00
30 minutes
(factory setting)
This function is used to set the automatic
reset time with the temperature setting.
01
15 minutes
02
60 minutes
03
90 minutes
F5
Automatic reset
temperature for
cooling
X
19-24
(19-24) ºC
This function is used to set the automatic
temperature reset in FAN/COOL/DRY
modes.
25
25 °C
(factory setting)
26-30
(26-30) ºC
F6
Automatic reset
temperature for
heating
X
17-20
(17-20) ºC
This function is used to set the automatic
temperature reset in HEAT mode.
21
21 ºC
(factory setting)
22-30
(22-30) ºC
F7
(*7)
Operation stoppage
prevention by remote
control switch
operational error
X
00
Not activated function
This function is used to prevent the
careless operational stoppage caused by
remote control switch operational error.
01
Activated function
F8
Lock function for
operation mode
selection
X
00
Not activated function
This function is used to prevent changes to
the operating mode.
01
Activated function
(factory setting)
F9
Lock function for
temperature setting
X
00
Not activated function
This function is used to prevent changes to
the temperature setting.
01
Activated function
(factory setting)
FA
Lock function for fan
speed selection
X
00
Not activated function
This function is used to prevent changes to
the fan speed.
01
Activated function
(factory setting)