10 Troubleshooting
Troubleshooting procedure
SMGB0091 rev.2 - 11/2015
232
Alarm code
38
Abnormality of protective circuit for protection (RASC unit)
The alarm code appears if 1~ 230V is supplied to the connector on the RASC unit PCB1 while Y52C (Compressor relay
open) is OFF or CMC (Magnetic contactor for compressor) or CMF (Magnetic contactor for fan motor) are open.
Is 1~ 230V applied
between PCN9 number 1
and 3 during stoppage?
Faulty RASC PCB1
Yes
Check wiring connection
except RASC PCB1
No
RASC PCB1 is normal
Connector number for check
Connector
PCN9
Pin number
1 and 3
Phenomenon
Cause
Check item
Action
(Turn OFF Main Switch)
Faulty DIP-IPM
Check DIP-IPM by
self-checking
Replace DIP-IPM
?
N O T E
• This alarm may appear if one of the protection devices of RASC unit is improperly connected or damaged (open-circuit fault) when
the operation is started.
• Besides this, check also Alarm Code: 02 Activation of RASC Unit Protection Device.