Specification of the components for a correct installation
Component
Manufacturer or specifications
Remarks
Auxiliary relay (X1)
OMRON mini power relay model:
MY1F or equivalent
Voltage between relay terminals 12 Vdc - 75 mA
Auxiliary relay (X3)
OMRON mini power relay model:
LY2F or equivalent
Voltage between relay terminals 12 Vdc
(SS1), (SS2), (x1), (x2) contact
example
Manual type
Voltage between terminals of the 230V - 5 mA contactor
3P connector cable
Optional part PCC-1A
(capable of connecting
the JST XHP –3 connector)
Five wires with connectors as one set
Wire (control) Voltage: 12V DC
0.5 mm²
Wire (power)
Voltage: 230V
2.0 mm²
?
N O T E
• The connection of the input signal is only an example.
• Keep the CN1 and CN2 wires as short as possible.
• Do not run transmission wiring along 230 V / 400 V CA power supply cables. Leave a distance of more than 30 cm between them.
(Intersection are occasionally allowed).
• If you install the wires along a power supply wire, insert the wires in a metal conduit tube and ground one end of the tube.
• The maximum wiring length is 70 m. If you use this function, it is recommended that you use safety devices such as an electrical
leakage breaker or a smoke detector.