10 Troubleshooting
Checking procedure for main parts
SMGB0091 rev.2 - 11/2015
269
10
10.4.2 Checking procedure for the inverter PCB
RASC-(4-6)HNPE
High voltage discharge work for replacing parts
High voltage discharge is an imperative work for replacing parts.
!
C A U T I O N
Electrical hazard. Risk of electrical shock. Perform this high voltage discharge work to avoid an electric shock.
1
Turn OFF the main switches and wait for three
minutes. Make sure that no high voltage exists. If
LED201 is ON after start-up and LED201 is OFF
after turning OFF power source, the voltage will
decrease lower than DC50V.
2
Connect connecting wires to an electrical soldering
iron.
3
Connect the wires to terminals, P and N on DIP-IPM.
=> Discharging is started, resulting in hot soldering
iron. Pay attention not to short-circuit between
terminal P(+) and N(-)
4
Wait for 2 or 3 minutes and measure the voltage
once again. Check to ensure that no voltage is
charged.
DIP-IPM
Connecting
wires
Electrical
soldering iron
Plug
Inverter module checking procedure
Rectifier circuit of inverter PCB
Remove all the terminals of the inverter PCB before
checking.
Non-faulty if [1] – [8] are checked and satisfied.
Measure with 1 kΩ range of a tester.
Internal circuit of rectified part of DIP-IPM
R
S
T
52C
㧙
1
Touch [+] of the tester to DIP-IPM 52C terminal,
and [-] to DIP-IPM R, S, T terminals to measure the
resistance. Normal if all three terminals have 1 kΩ or
greater.
2
Contrary to [1], touch [-] of the tester to DIP-IPM
52C terminal, and [+] to DIP-IPM R, S, T terminals to
measure the resistance. Normal if all three terminals
have 100 kΩ or greater.
3
Touch [-] of the tester to [-] of DIP-IPM DMI (soldered
part), and [+] of the tester to DIP-IPM R, S, T
terminals to measure the resistance. Normal if all
three terminals have 1 kΩ or greater.
4
Contrary to [3], touch [+] of the tester to [-] of DIP-
IPM DMI, and [-] of the tester to DIP-IPM R, S, T
terminals to measure the resistance. Normal if all
three terminals have 100 kΩ or greater.
Contact with specified
terminals to measure.
Tester