9 Servicing
Removing components
SMGB0091 rev.2 - 11/2015
149
9
9.3.5 Removing stop valve protection cover
Stop valves are located at the right side of RASC units,
next to the cycle service cover.
RASC units are factory-supplied with the stop valve
protection cover. Before connecting refrigerant piping, the
stop valve protection cover shall be removed:
1
Unscrew the 4 fixing screws.
2
Remove the protection cover.
Screws
Gas stop valve
Liquid stop valve
9.3.6 Removing upper cover
1
Unscrew the 35 fixing screws.
2
Lift the upper cover upward. Then, remove it and leave
it away to a side carefully.
!
C A U T I O N
• Wires are attached to the upper cover by 3 clamps at the front
side and 3 clamps at the back side. Remember to release
them before lifting the upper cover.
• When lifting up the upper cover, at least two people are
required (one from each side).
Upper cover
Clamps
9.3.7 Removing air inlet panel
1
Unscrew the 3 fixing screws.
2
Remove the thermistor for outdoor ambient
temperature from the air inlet panel grill cutting the
cable ties.
3
Slide the air inlet panel upward. Then, pull backwards
and remove it.
Screws
Thermistor for outdoor ambient
temperature (THM7)