5 Control system
Standard operation sequence
SMGB0091 rev.2 - 11/2015
83
5
Pressing
RUN/STOP
switch
Stop of inverter
Stop of MC
I.U:
Indoor unit
R.U:
RASC unit
MD: OFF
Power to CMC: OFF
Power to MIF: OFF
Temperature
on the top of
compressor
After
3 minute
20 seconds
(For unit with drain pump)
> 80 ºC
< 75 ºC
Power to CH: ON
Power to CH: OFF
Power to Y52C: OFF
Stop of MOF
Power to YH2: OFF
Yes
No
STOP
Power to
indoor unit:
OFF
Power to
RASC unit:
OFF
LCD indication: OFF
Power to PCB in indoor unit: OFF
Power to CH: OFF
Power to PCB in RASC unit: OFF
RUN/STOP lamp: OFF
DRY, set fan speed & set temp. indication: continuously ON
from 1
Pressing
AUTO-LOUVER switch
Stop of
AUTO-LOUVER
Start of
AUTO-LOUVER
Alternatively
Only for air panel
or indoor unit with
auto-louver