Spindle type
Nº
Description
Remarks
Cap
Allen wrench
Hex 4 mm
Refrigerant piping
Field supplied
Flare nut
Refrigerant pressure To RASC unit
Seat Surface
Fully closed position
Check joint
Only the charging those can be connected
Charge port cap
O-Ring
Rubber
Spindle valve
Open – Counterclockwise
Close – Clockwise
«
Shaft
¬
Pin
Stopper
(a) Closed
This valve is opened or closed with rotating 90 degrees at
the ball valve part. Rotate the shaft until the pin touches
the stopper. Do not apply the extra force. Use a slotted
screwdriver to control the shaft. Do not leave the ball valve
partly open
(b) Opened
Ball type
(a)
(b)
Do not apply two
spanners at this
position. If applied,
leakage will occur.
Stop valve
(Spindle type)
Flare nut
Use two spanners
here for pipe
connection
Do not work with
two spanners
here.
Refrigerant
leakage shall
occur
Position to apply
spanners
Don not apply two
spanners work here
Spindle type
Ball type
!
C A U T I O N
•
At the test run, fully open the spindle and ball stop valve.
•
If not fully opened, the devices will be damaged.
•
Do not attempt to turn service valve rod beyond its stop.
•
Do not loosen the stop ring. If the stop ring is loosened, it is dangerous since the spindle will hop out.
•
An excess or a shortage of refrigerant is the main cause of trouble to the units. Charge the correct refrigerant quantity according to the
description of label at the inside of service cover.
•
Check for refrigerant leakage in detail. If a large refrigerant leakage occurs, it will cause difficulty with breathing or harmful gases would
occur if a fire was being used in the room.
3 Piping work and refrigerant charge
Piping connection for RASC unit
SMGB0091 rev.2 - 11/2015
36