10 Troubleshooting
Troubleshooting in check mode
SMGB0091 rev.2 - 11/2015
263
10
Cause of indoor unit stoppage (
dA
)
Indication
Contents
?
N O T E
•
10
Demand thermo OFF:
32
30
28
26
24
22
20
5
10
15
20
25
(
o
C)
(
o
C)
29
23
23
26
21
19
17
Temperature Area in Heating Operation
Outdoor temperature
Thermo-OFF temperature area
Forced stoppage
temperature area
Air inlet temperature of indoor unit
Restart
temperature area
• The cause code for indoor unit stoppage is not always
“
02
“ (Alarm) during stoppage by the abnormality.
If the unit is under Thermo-OFF by other cause of stoppage
before ”
02
“ (Alarm) occurs, the previous cause code for
indoor unit stoppage remains.
• When the transmitting between the inverter PCB and the
RASC unit PCB1 is disconnected for 30 seconds, the
RASC micro-computer will be reset. Accordingly when the
alarm code “
04
” (Abnormal Transmitting between Inverter
PCB and RASC Unit PCB1) occurs, the cause code for
indoor unit stoppage may be indicated “
05
”.
• When the transmitting between the indoor unit and the
RASC unit is disconnected for 3 minutes, the indoor
micro-computer will be reset. Accordingly when the alarm
code “
03
” (Abnormal Transmitting between Indoor Unit
and RASC Unit) occurs, the cause code for indoor unit
stoppage may be indicated “
06
”.
• For combinations with several indoor units, if the cause
code for indoor unit stoppage “
21
” is indicated, check the
cause of stoppage for other indoor units.
00
Operation OFF, Power OFF
01
Thermo-OFF, float switch activation (NOTE 1)
02
Alarm (NOTE 2)
03
Freeze protection, overheating protection
05
Instantaneous power failure at RASC unit (NOTE 3)
06
Instantaneous power failure at indoor unit (NOTE 4)
07
Stoppage of cooling operation due to low outdoor air
temperature
Stoppage of heating operation due to high outdoor air
temperature
10
Demand
11
Retry due to compression ratio decrease
13
Retry due to high pressure increase prevention
15
Vacuum/discharge gas temperature increase retry
16
Retry due to discharge gas superheat decrease
17
Retry stop due to inverter trip (Instantaneous over-
current, electronic thermal activation, current sensor
abnormality)
18
Retry stop due to inverter trip (Voltage decrease, over-
voltage, transmission error, micro-controller reset, etc.)
19
Deviation of expansion valve opening
21
Forced Thermo-OFF
22
Outdoor hot start control
26
Retry due to high pressure decrease
28
Cooling air discharge temperature decrease
33
Forced Thermo-OFF
34
Forced Thermo-OFF
35
Retry due to abnormal operating mode
(Reversing valve switching failure)
Cancellation of Forced Thermo OFF (Cause code:
21
)
Turn ON the power source and wait for more than 30 seconds. Then press PSW1 for more than 3 seconds.
Forced thermo-OFF (indoor unit error code
21
) will be cancelled.
However, this function may damage the compressor, use only on inevitable occasion.
• In case of using the remote control switch (PC-ART), the cancellation is also available with it.
•
When “Operation Lock” indication flashes on the remote control LCD, press FAN SPEED and LOUVER switches
simultaneously for more than 3 seconds.
• “Operation Lock” Indication is disappeared and operation is available.