4 Electrical and control settings
Setting and function of DIP and RSW switches for RASC units
SMGB0091 rev.2 - 11/2015
69
4
4.6.3 Jumper lead setting (JP1~6)
Setting before shipment:
System
JP1
JP2
JP3
JP4
JP5
JP6
Three-phase (3N~)
1
1
0
1
0
0
?
N O T E
•
0: Open
•
1: Short circuit
The function selection using the jumper lead setting is shown in the tables below:
Setting
Function
Details
JP1
Not used
-
JP2
Not used
-
JP3
400V power
source voltage
When JP3 is set to “open”, current protection
parameters are set for a 400 V power source
voltage.
JP4
Fixing for cooling
only
When JP4 is set to “open”, operation mode is fixed
for cooling. Thermo-ON is available only by “COOL”
or “DRY” mode at indoor unit.
JP5
Self diagnosis
For function test of the RASC unit control PCB.
Factory default setting is open. When power ON in
short condition it enters self diagnosis.
JP6
Phase detection
release
Phase detection abnormality not detected. When
short, doesn’t affect phase detection.
4.6.4 LED’s indication
LED Indication
LED1
Red
This LED indicates the transmission status between
the indoor unit and the RCS
LED2
Yellow
This LED indicates the transmission status between
the indoor unit and the RASC unit
LED3
Green
Power source for the PCB