3 Piping work and refrigerant charge
Refrigerant piping range
SMGB0091 rev.2 - 11/2015
45
3
4 indoor units system
•
Case a)
?
N O T E
If the capacity ratio between IU group 1+2 and 3+4
is higher than 60/40%, install a line branch system or
contact with your Hitachi dealer.
(mm)
Multi-kit
(mm)
Multi-kit
RASC
unit
Pipe Size (A)
Total indoor
unit capacity
after first
branch
(1+2) or (3+4)
Pipe Size (B,C)
Gas
Liquid
TE option
TW option
Gas
Liquid
TE option
TW option
4 HP
Ø15.88
Ø9.52
TE-04N1
TW-52AN
(0.8-1.5) HP
Ø12.7
Ø6.35
TE-03N1
TW-22AN
(5/6) HP
Ø15.88
Ø9.52
TE-56N1
TW-52AN
(1.8/2.0) HP
Ø15.88
Ø6.35
TE-03N1
TW-52AN
8 HP
Ø25.4
Ø9.52 (*)
TE-08N
TW-102AN
≥ 2.3 HP
Ø15.88
Ø9.52
<4HP: TE-03N1
=4HP: TE-04N1
≥5HP: TE-56N1
TW-52AN
10 HP
Ø25.4
Ø12.7
TE-10N
TW-102AN
(*): In case that pipe length (A+B+(C or D) or A+C+(F or G))
exceeds 70m in 8 HP, please use a Ø12.7 pipe as a liquid
pipe.
The dimensions for TRE and TW multi-kits are different. Refer
to the Indoor units’ Technical Catalogue in order to check the
dimensions.
(mm)
Indoor unit
capacity
Pipe Size (D,E,F,G)
Gas
Liquid
(0.8-1.5) HP
Ø12.7
Ø6.35
(1.8/2.0) HP
Ø15.88
Ø6.35
≥ 2.3HP
Ø9.52
Ø6.35
Connections including 8.0HP or 10.0HP indoor units are not
possible.
•
Case b)
(mm)
Multi-kit
(mm)
RASC unit
Pipe Size (A)
Indoor unit
capacity
Pipe Size (B,C,D,E)
Gas
Liquid
Gas
Liquid
8 HP
Ø25.4
Ø9.52 (*)
QE-812N1
(0.8-1.5) HP
Ø12.7
Ø6.35
10 HP
Ø25.4
Ø12.7
(1.8/2.0) HP
Ø15.88
Ø6.35
≥ 2.3HP
Ø15.88
Ø9.52
(*): In case that pipe length (A+B or A+C or A+D or A+E) exceeds 70m
in 8 HP, please use a Ø12.7 pipe as a liquid pipe.
Connections including 8.0HP or 10.0HP indoor units
are not possible.