7 Commissioning
Test run procedure using the remote control switch (PC-ARF)
SMGB0091 rev.2 - 11/2015
122
8
To finish the test run, press “
” (run/stop) again or pass
over the set test run time. When changing the test run time,
press “ ” or “
” to select “T-RUN TIME”. Then, set the test
run time (30 to 600 minutes) by pressing “ ” or “ ”
Test Run: 2 units
MODE
SPEED
MED
COOL
LOUV.
SEL.
ADJ
T-RUN TIME 510MIN
STOP
•
The RUN indicator on the remote control switch flashes
when some abnormalities such as protection devices
activated occur during the test run as well as the RUN
indicator (orange) on the indoor unit flashes (0.5 second
ON/ 0.5 second OFF). Additionally, the alarm code, the
unit model code and connected number of indoor units will
be displayed on the LCD as shown in the figure below. If
the RUN indicator on PC-ARF flashes (2 seconds ON/
2 seconds OFF), it may be a failure in the transmission
between the indoor unit and the remote control switch
(loosening of connector, disconnecting wiring or breaking
wire, etc.). In this case, check the item
and perform for troubleshooting. Consult to authorized
service engineers if abnormality can not be recovered.
SEL.
OP MODE
MODEL : b .02
Alarm Code:
22
01-02
ALM RST
ADDR
ENT.
OK
: b . 02
:
22
01 - 02
Refrigerant cycle number
of Indoor unit which
abnormality occurs
Indoor unit number which
abnormality occurs
Alarm code number
Alarm code
Unit model code
Total number of Indoor unit in
same refrigerant cycle as one
that abnormality occurs
MODEL