4.3 Electrical connection of the RASC unit
!
C A U T I O N
Check to ensure that the field supplied electrical components (mains power switches, circuit breakers, wires, connectors and wire
terminals) have been properly selected according to the electrical data indicated on this chapter and they comply with national and local
codes. If it is necessary, contact with your local authority in regards to standards, rules, regulations, etc.
4.3.1 Wiring size
Recommended minimum sizes for field provided wires:
Model
Power supply
Max. current
(A)
Power supply cable size
Transmitting cable size
EN60 335-1
EN60 335-1
RASC-4HNPE
3N~ 400V 50Hz
14.1
4 x 4.0mm
2
+ GND
2 x 0.75mm
2
RASC-5HNPE
14.1
4 x 4.0mm
2
+ GND
RASC-6HNPE
16.0
4 x 4.0mm
2
+ GND
RASC-8HNPE
24.7
4 x 6.0mm
2
+ GND
RASC-10HNPE
24.7
4 x 6.0mm
2
+ GND
?
N O T E
Use wires which are not lighter than the polychloroprene sheathed flexible cord (code designation 60245 IEC 57).
4.3.2 Minimum requirements of the protection devices
!
C A U T I O N
•
Ensure specifically that there is an Earth Leakage Breaker (ELB) installed for the units (RASC and indoor unit).
•
If the installation is already equipped with an Earth Leakage Breaker (ELB), ensure that its rated current is large enough to hold the
current of the units (RASC and indoor).
?
N O T E
•
Electric fuses can be used instead of magnetic Circuit Breakers (CB). In that case, select fuses with similar rated values as the CB.
•
The Earth Leakage Breaker (ELB) mentioned on this manual is also commonly known as Residual Current Device (RCD) or Residual
Current Circuit Breaker (RCCB).
•
The Circuit Breakers (CB) are also known as Thermal-Magnetic Circuit Breakers or just Magnetic Circuit Breakers (MCB).
Main switch protection
Select the main switches in according to the next table:
Model
Power source
Max. current
(A)
CB
(A)
ELB
(no. poles/A/mA)
RASC-4HNPE
3N~ 400V 50Hz
14.1
20
4/40/30
RASC-5HNPE
14.1
20
RASC-6HNPE
16.0
20
RASC-8HNPE
24.7
30
RASC-10HNPE
24.7
30
ELB: Earth leakage breaker; CB: Circuit breaker
4 Electrical and control settings
Electrical connection of the RASC unit
SMGB0091 rev.2 - 11/2015
62