3.3.3 Piping system (Line branch installation)
RASC unit
4 HP
5 HP
6 HP
8 HP
10 HP
Allowed quantity of indoor units
2 - 5 (*)
2 - 6 (*)
(*): In case of more than 4 indoor units, please respect the restrictions shown in section
Combinability
of the Technical Catalogue.
Maximum refrigerant piping length (Line branch installation)
(m)
Item
4HP
5HP
6HP
8HP
10HP
Maximum piping length between the
RASC unit and the farthest indoor unit
Actual piping length (L1)
75
100
Equivalent piping length (EL)
95
125
Maximum total piping length (L1+ L3
1
+ L3
2
+ ... + L3
n-1
)
95
100
145
Maximum piping length from the 1st multikit to the furthest indoor unit (L2)
30
40
Maximum piping length between multikit and indoor unit (L3
1
, L3
2
, L3
3
, ..., L3
n
)
10
15
Maximum height difference between
RASC unit and indoor unit (Hi-o)
RASC unit higher than indoor unit
30
Indoor unit higher than RASC unit
20
Maximum height difference between indoor units (Hi)
10
Maximum height difference between multikits and between multikit and indoor unit
3
3 Piping work and refrigerant charge
Refrigerant piping range
SMGB0091 rev.2 - 11/2015