6 Optional functions
Optional functions
SMGB0091 rev.2 - 11/2015
110
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
bb
Cooling temperature
compensation
X
00
Standard setting.
No compensation
This function is used to obtain longer
cooling periods. When this function is
enabled, Thermo-ON/OFF is controlled
under lower temperature conditions than
the setting temperature by the remote
control switch.
01
It decrease the
temperature -1ºC
02
It decrease the
temperature -2ºC
bC
Not available
–
00
Not available
–
01
(Used as 00 conditions)
bd
Not available
–
00
Not available
–
01
(Used as 00 conditions)
bE
Not available
–
00
Not available
–
01
(Used as 00 conditions)
C1
Not available
–
00
Not available
–
01
(Used as 00 conditions)
C2
Not available
–
“- -”
permanent
Not available
–
C3
Not available in the
European market
O
00
Not available
–
01
(Used as 00 conditions)
C4
Drain pump in
heating mode
O
00
Not activated function
This function is used to activate the drain
pump in heating mode.
01
Activated function
C5
Static pressure
selection (RPI)
O
00
Standard static pressure
(factory set)
This function is used to change the static
pressure of the RPI units from the remote
control.
01
High static pressure
02
Low static pressure
Increasing fan speed
00
Not available
This function is used to change the indoor
units fan speed installed in high ceilings.
01
Hi Speed 1 (*3)
02
Hi Speed 2 (*3)
C6
High speed at
heating Thermo-OFF
O
00
Not activated function
This function is used to increase the fan
speed when the thermostat reaches the
set temperature in heating using function
C5.
01
Activated function
C7
Cancellation of the
forced compressor
operation for at least
3 minutes
O
00
Not activated function
This function is used to cancel the function
b3 (Forced compressor operation for at
least 3 minutes).
01
Activated function
C8
Thermistor of remote
control switch
O
00
Not available
This function determines the thermistor to
control the air temperature.
?
N O T E
If THM-R2AE accessory is installed, these
setting have different meaning.
01
Air temperature control
using the remote
control thermistor
02
Air temperature
control using the
average value of the
air inlet thermistor and
the remote control
thermistor
C9
Not available
–
“- -”
permanent
Not available
–
CA
Not available
–
“- -”
permanent
Not available
–