5
After connecting the refrigerant piping, seal the open space between knockout hole and refrigerant pipes by using
insulation material.
Unit
Side
Nº
Description
Insulation Material
Insulation Material
Field Supplied
Insulation Material
6
Operation of stop valve should be performed according to the indications below:
RASC unit stop valve
1
Remove the stop valve cap before performing the air tight test after connecting the flare nut. Tighten the spindle valve
in clockwise according to the following table “Tightening Torque of Stop Valves”.
2
Tighten the flare nut according the specified torque. If the tightening torque is excessive, it may cause refrigerant
leakage from the spindle part.
3
Perform the air tight test after the tightening work. It is more effective to perform this work after fix the flare nuts for
the piping connection to the stop valves.
4
Use the charging hose for the check joint connection. When removing the charging hose from the check joint, a
sound may be heard by a small quantity of refrigerant leak. However it is not abnormality. Do not apply excessive
force to the end of opening the spindle. (Tightening Torque: < 5.0 N·m).
RASC unit stop valve
Spindle type
Ball type
Liquid
Gas
(a)
Spindle valve
Flare nut
Cap
Check joint for service port
Tightening Torque (N.m)
Liquid valve
7-9
40
10HP: 60
33-42
14-18
Gas valve
-
80
8/10HP: 100
20-25
3 Piping work and refrigerant charge
Piping connection for RASC unit
SMGB0091 rev.2 - 11/2015
35
3