3 Piping work and refrigerant charge
Refrigerant piping range
SMGB0091 rev.2 - 11/2015
44
3 indoor units system
(mm)
Multi-kit
(**)
RASC unit
Pipe Size (A)
Gas
Liquid
TRE option
TG option
(4-6) HP
Ø15.88
Ø9.52
TRE-46N1
TG-53AN
8 HP
Ø25.4
Ø9.52 (*)
TRE-812N1
TG-103AN
10 HP
Ø25.4
Ø12.7
TRE-812N1
(**)
TG-103AN
(**)
• (*): In case that pipe length (A+B or A+C or A+D) exceeds 70m in 8 HP, please
use a Ø12.7 pipe as a liquid pipe.
• (**): In case of combinations with 8.0HP or 10.0HP indoor units, install a line
branch system with multi-kits E-162SN3 and E-102SN3.
• The dimensions for TRE and TG multi-kits are different. Refer to the Indoor
units’ Technical Catalogue in order to check the dimensions.
(mm)
Indoor unit capacity
after branch
Pipe size (B, C)
Gas
Liquid
(0.8-1.5) HP
Ø12.7
Ø6.35
(1.8/2.0) HP
Ø15.88
Ø6.35
(2.3-6.0) HP
Ø15.88
Ø9.52
8.0 HP
Ø19.05
Ø9.52
10.0 HP
Ø22.20
Ø9.52