5 Control system
Standard control functions
SMGB0091 rev.2 - 11/2015
92
5.4.4 Preheating control of compressor
During stopped compressor
During operating compressor
< 75ºC
Power to CH: ON
Temp
at top of
compressor
Power to CH: OFF
Temp
at top of
compressor
≥ 75ºC
> 80ºC
≤ 80ºC
Power to RASC unit: ON
Power to CH: ON
Temp
at top of
compressor
Power to CH: OFF
Temp
at top of
compressor
≥ Condensing
tempe15ºC
Power to RASC unit: ON
Compressor: ON
< Condensing tempe15ºC
≤ Condensing
tempe20ºC
> Condensing tempe20ºC
5.4.5 Prevention control for high pressure increase during cooling operation
This function is performed to prevent the abnormal condition (Alarm Code: 02) when the air flow volume is abnormally
decreased. When the following conditions are met, the forced Thermo-OFF operation is performed.
1
Y52C is turned “ON” during the cooling operation.
2
High Pressure ≥ 3.8 MPa.
The cause of stoppage is “13” during Thermo-OFF.