10 Troubleshooting
Troubleshooting procedure
SMGB0091 rev.2 - 11/2015
201
10
Alarm code
02
Activation of the safety device in the RASC unit
This alarm is indicated when one of safety devices is activated during compressor running.
Does CMC or
CMF turn ON when
starting?
Faulty PCB1.
No
Yes
Is the voltage 230V
existing at the #1 to
#3 of PCN9 during
Y52C is ON?
No
Is the protective
device still operating?
No
Does CMC or
CMF turn ON
for more than
3 seconds?
Yes
No
Yes
Yes
Normal PCB1
Is the CMC
or CMF coil
damaged?
Is the protective
device still operating?
Yes
Faulty CMC or CMF
or disconnected
cables
No
Yes
No
Yes
If all the above checks have been overcome, see the status of the following items in this order:
(Check if some of the following devices terminals connected to the PCN8 are open/activated by using a tester)
Activation of the float switch (FS)
Activation of the internal thermostat protection of the motor (ITO)
Activation of the high pressure switch (PSH: 4.15 MPa)
Variable frequency driver failure (VFD)
PCN8: Safety devices line scheme
?
N O T E
Please, refer to the table on the following page in order to know the specific details of each device.