7 Commissioning
Test run procedure using the wireless remote control switch (PC-LH3A)
SMGB0091 rev.2 - 11/2015
126
c.
Alarm code display
-
If some malfunction occurs because of the activation of a safety device or any other reason, the red RUN LED
blinks (0.5 seconds ON / 0.5 seconds OFF).
-
Refer to section
.
-
The alarm code displays the number of blinks of the green DEF LED and the yellow FILTER LED as shown
bellow:
-
Green DEF LED: Digit 2 of the alarm code blinks.
-
Yellow FILTER LED: Digit 1 of the alarm code blinks. (Alphabet code: A=10 blinks, B=11 blinks, C=12 blinks, etc.).
Example:
Yellow FILTER LED
Green DEF LED
DEF LED blinks three times
(0.5 seconds ON / 0.5 seconds OFF)
FILTER LED blinks 5 times.
(0.5 seconds ON / 0.5 seconds OFF)
Alarm code:
The red RUN LED (1 second ON / 1 second OFF) means that there is an abnormal transmission between the indoor
units and the RASC unit.