Proline Cubemass C 300
Commissioning
Hauser
83
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
entry / User
interface
Factory setting
Select medium type
–
Use this function to select the
type of medium: "Gas" or
"Liquid". Select the "Other"
option in exceptional cases in
order to enter the properties of
the medium manually (e.g. for
highly compressive liquids
such as sulfuric acid).
• Liquid
• Gas
• Other
Liquid
Select gas type
In the
Medium selection
submenu, the
Gas
option is
selected.
Select measured gas type.
• Air
• Ammonia NH3
• Argon Ar
• Sulfur hexafluoride
SF6
• Oxygen O2
• Ozone O3
• Nitrogen oxide
NOx
• Nitrogen N2
• Nitrous oxide N2O
• Methane CH4
• Methane CH4 +
10% Hydrogen H2
• Methane CH4 +
20% Hydrogen H2
• Methane CH4 +
30% Hydrogen H2
• Hydrogen H2
• Helium He
• Hydrogen chloride
HCl
• Hydrogen sulfide
H2S
• Ethylene C2H4
• Carbon dioxide
CO2
• Carbon monoxide
CO
• Chlorine Cl2
• Butane C4H10
• Propane C3H8
• Propylene C3H6
• Ethane C2H6
• Other
Methane CH4
Reference sound velocity
In the
Select gas type
parameter, the
Other
option is
selected.
Enter sound velocity of the gas
at 0 °C (32 °F).
1 to 99
999.9999 m/
s
415.0 m/s
Temperature coefficient sound
velocity
In the
Select gas type
parameter, the
Other
option is
selected.
Enter the temperature
coefficient for the gas sound
velocity.
Positive floating
point number
0.87 (m/s)/K
Pressure compensation
–
Select pressure compensation
type.
• Off
• Fixed value
• External value
• Current input 1
• Current input 2
Off