Proline Cubemass C 300
Commissioning
Hauser
87
Parameter overview with brief description
Parameter
Description
Selection / User interface /
User entry
Factory setting
Assign status input
Select function for the status input.
• Off
• Reset totalizer 1
• Reset totalizer 2
• Reset totalizer 3
• Reset all totalizers
• Flow override
• Zero adjustment
• Reset weighted averages
• Reset weighted av
totalizer 3
Off
Terminal number
Shows the terminal numbers used by the
status input module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
–
Active level
Define input signal level at which the
assigned function is triggered.
• High
• Low
High
Response time status input
Define the minimum amount of time the
input signal level must be present before the
selected function is triggered.
5 to 200 ms
50 ms
*
Visibility depends on order options or device settings
10.4.7 Configuring the current output
The
Current output
wizard guides you systematically through all the parameters that have
to be set for configuring the current output.
Navigation
"Setup" menu → Current output
‣
Current output 1 to n
Terminal number
Signal mode
Process variable current output
Current range output
Lower range value output
Upper range value output
Fixed current
Damping current output
Failure behavior current output
Failure current