Proline Cubemass C 300
Commissioning
Hauser
131
Via Web browser, FieldCare, DeviceCare (via CDI-RJ45 service interface), fieldbus
You can only obtain a reset code from your local Hauser service organization.
The code must be calculated explicitly for every device.
1. Note down the serial number of the device.
2. Read off the
Operating time
parameter.
3. Contact the local Hauser service organization and tell them the serial
number and the operating time.
Get the calculated reset code.
4. Enter the reset code in the
Reset access code
The access code has been reset to the factory setting
0000
. It can be redefined
For IT security reasons, the calculated reset code is only valid for 96 hours from the
specified operating time and for the specific serial number. If you cannot return to the
device within 96 hours, you should either increase the operating time you read out by
a few days or switch off the device.
10.7.2 Write protection via write protection switch
Unlike parameter write protection via a user-specific access code, this allows the user to
lock write access to the entire operating menu - apart from the
"Contrast display"
parameter
.
The parameter values are now read only and cannot be edited any more (exception
"Contrast display" parameter
):
• Via local display
• Via HART protocol
1.
ON
OFF
1
2
3
4
A0029630
Setting the write protection (WP) switch on the main electronics module to the
ON
position enables hardware write protection.
In the
Locking status
parameter, the
Hardware locked
option is displayed
→ 133. In addition, on the local display the symbol appears in front of the
parameters in the header of the operational display and in the navigation view.
X X X X
X X X
X
X
20.50
XX
XX
A0029425