Commissioning
Proline Cubemass C 300
90
Hauser
Parameter
Prerequisite
Description
User interface /
Selection / User
entry
Factory setting
Current range output
–
Select current range for
process value output and
upper/lower level for alarm
signal.
• 4...20 mA NE
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
• 4...20 mA (4...
20.5 mA)
• 0...20 mA (0...
20.5 mA)
• Fixed value
Depends on country:
• 4...20 mA NE
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
Lower range value output
One of the following options is
selected in the
Current span
parameter (→ 90):
• 4...20 mA NE (3.8...20.5
mA)
• 4...20 mA US (3.9...20.8
mA)
• 4...20 mA (4... 20.5 mA)
• 0...20 mA (0... 20.5 mA)
Enter lower range value for the
measured value range.
Signed floating-point
number
Depends on country:
• 0 kg/h
• 0 lb/min
Upper range value output
One of the following options is
selected in the
Current span
parameter (→ 90):
• 4...20 mA NE (3.8...20.5
mA)
• 4...20 mA US (3.9...20.8
mA)
• 4...20 mA (4... 20.5 mA)
• 0...20 mA (0... 20.5 mA)
Enter upper range value for
the measured value range.
Signed floating-point
number
Depends on country
and nominal
diameter
Fixed current
The
Fixed current
option is
selected in the
Current span
Defines the fixed output
current.
0 to 22.5 mA
22.5 mA
Damping current output
A process variable is selected
in the
Assign current output
parameter (→ 89) and one
of the following options is
selected in the
Current span
parameter (→ 90):
• 4...20 mA NE (3.8...20.5
mA)
• 4...20 mA US (3.9...20.8
mA)
• 4...20 mA (4... 20.5 mA)
• 0...20 mA (0... 20.5 mA)
Set reaction time for output
signal to fluctuations in the
measured value.
0.0 to 999.9 s
1.0 s
Failure behavior current output
A process variable is selected
in the
Assign current output
parameter (→ 89) and one
of the following options is
selected in the
Current span
parameter (→ 90):
• 4...20 mA NE (3.8...20.5
mA)
• 4...20 mA US (3.9...20.8
mA)
• 4...20 mA (4... 20.5 mA)
• 0...20 mA (0... 20.5 mA)
Define output behavior in
alarm condition.
• Min.
• Max.
• Last valid value
• Actual value
• Fixed value
Max.
Failure current
The
Defined value
option is
selected in the
Failure mode
parameter.
Enter current output value in
alarm condition.
0 to 22.5 mA
22.5 mA
*
Visibility depends on order options or device settings