Electrical connection
Proline Cubemass C 300
38
Hauser
HART input
2
4...20 mA
4
1
2
3
3
6
5
A0028763
13
Connection example for HART input with a common negative (passive)
1
Automation system with HART output (e.g. PLC)
2
Active barrier for power supply (e.g. RN221N)
3
Cable shield provided at one end. The cable shield must be grounded at both ends to comply with EMC
requirements; observe cable specifications
4
Analog display unit: observe maximum load → 181
5
Pressure transmitter (e.g. Cerabar M, Cerabar S): see requirements
6
Transmitter
Current output 4-20 mA
4...20 mA
2
1
3
A0028758
14
Connection example for 4-20 mA current output (active)
1
Automation system with current input (e.g. PLC)
2
Analog display unit: observe maximum load → 181
3
Transmitter
2
4...20 mA
3
1
4
A0028759
15
Connection example for 4-20 mA current output (passive)
1
Automation system with current input (e.g. PLC)
2
Active barrier for power supply (e.g. RN221N)
3
Analog display unit: observe maximum load → 181
4
Transmitter