Parameter 16-85 FC Port CTW 1
Table 898: Parameter 16-85 FC Port CTW 1
16-85 FC Port CTW 1
Default value: 0
Parameter type: Range, 0 - 65535
Setup: All setups
Conversion index: 0
Data type: V2
Change during operation: False
View the 2-byte control word (CTW) received from the fieldbus master. Interpretation of the control word depends on the fieldbus
option installed and the control word profile selected in
parameter 8-10 Control Word Profile
.
Parameter 16-86 FC Port REF 1
Table 899: Parameter 16-86 FC Port REF 1
16-86 FC Port REF 1
Default value: 0
Parameter type: Range, -200 - 200
Setup: All setups
Conversion index: 0
Data type: N2
Change during operation: False
View the 2-byte status word (STW) sent to the fieldbus master. Interpretation of the status word depends on the fieldbus option
installed and the control word profile selected in
parameter 8-10 Control Word Profile
.
Parameter 16-87 Bus Readout Alarm/Warning
Table 900: Parameter 16-87 Bus Readout Alarm/Warning
16-87 Bus Readout Alarm/Warning
Default value: 0
Parameter type: Range, 0 - 65535, Array [3]
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: False
Alarm and warning numbers in hex as shown in the alarm log. The high byte contains the alarm, the low byte contains the warning.
The alarm number is the 1
st
that occurred after the last reset.
Parameter 16-88 Fieldbus Torque FF
Table 901: Parameter 16-88 Fieldbus Torque FF
16-88 Fieldbus Torque FF
Default value: 0
Parameter type: Range, -200 - 200
Setup: 1 setup
Conversion index: 0
Data type: N2
Change during operation: True
A PCD write reference parameter. This parameter allows the PLC to adjust the Torque FF over the fieldbus continuously as a per-
centage of motor nominal torque, see
parameter 1-26 Motor Cont. Rated Torque
.
Parameter 16-89 Configurable Alarm/Warning Word
Table 902: Parameter 16-89 Configurable Alarm/Warning Word
16-89 Configurable Alarm/Warning Word
Default Value: 0
Parameter Type: Range, 0 - 65535
Setup: All setups
Conversion Index: 0
Data Type: Uint16
Change during operation: False
This alarm/warning word is configured in parameter
8-17 Configurable Alarm and Warningword
to match the actual requirements.
5.16.7 16-9* Diagnosis Readouts
For details of bit descriptions, refer to
AU275636650261en-000101 / 130R0334 | 513
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide