Option Name
Description
[132]
Feedback 4–
20mA
[133]
Motor cur. 4–
20mA
The value is taken from
parameter 16-37 Inv. Max. Current
. The inverter maximum current (160%
current) is equal to 20 mA. Example: Inverter normal current (11 kW) is 24 A. 160% = 38.4 A. Motor
normal current is 22 A, the readout is 11.46 mA.
16 mA × 22
A
38 . 4
A
= 13 . 17 mA
If the normal motor current is equal to 20 mA, the output setting of
parameter 6-52 Terminal 42
Output Max Scale
is:
I
VLT, MAX
× 100
I
Motor, Nom
= 38 . 4 × 100
22
= 175 %
[134]
Torq.% lim 4–
20mA
The torque setting is related to the setting in
parameter 4-16 Torque Limit Motor Mode
.
[135]
Torq.% nom 4–
20mA
The torque setting is related to the motor torque setting.
[136]
Power 4–20mA
Taken from
parameter 1-20 Motor Power [kW]
.
[137]
Speed 4–20mA
Taken from
parameter 3-03 Maximum Reference
. 20 mA = value in
parameter 3-03 Maximum Refer-
ence
.
[138]
Torque 4–20mA
Torque reference related to 160% torque.
[139]
Bus ctrl.
An output value set from fieldbus process data. The output works independently of internal func-
tions in the drive.
[140]
Bus ctrl. 4–20mA
An output value set from fieldbus process data. The output works independently of internal func-
tions in the drive.
[141]
Bus ctrl t.o.
Parameter 4-54 Warning Reference Low
defines the behavior of the analog output in case of field-
bus timeout.
[142]
Bus ctrl 4-20mA
t.o.
Parameter 4-54 Warning Reference Low
defines the behavior of the analog output in case of field-
bus timeout.
[147]
Main act val
[148]
Main act val
4-20mA
[149]
Torque % lim
4-20mA
Analog output at 0 torque is 12 mA. Motoring torque increases the output current to maximum
torque limit 20 mA (set in
parameter 4-16 Torque Limit Motor Mode
). Generating torque decreases
the output to torque limit in generator mode (set in
parameter 4-17 Torque Limit Generator Mode
)
Example:
Parameter 4-16 Torque Limit Motor Mode
= 200% and
parameter 4-17 Torque Limit Genera-
tor Mode
= 200%. 20 mA = 200% motoring and 4 mA = 200% generating.
[150]
Max Out Fr
4-20mA
0 Hz = 0 mA,
parameter 4-19 Max Output Frequency
= 20 mA.
[158]
Motor Volt.
[159]
Motor Volt.
4-20mA
AU275636650261en-000101 / 130R0334 | 251
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide