Parameter 6-53 Term 42 Output Bus Ctrl
Table 427: Parameter 6-53 Term 42 Output Bus Ctrl
6-53 Term 42 Output Bus Ctrl
Default value: 0%
Parameter type: Range, 0 - 100%
Setup: All setups
Conversion index: -2
Data type: N2
Change during operation: True
Holds the level of output 42 if controlled by bus.
Parameter 6-54 Term 42 Output Timeout Preset
Table 428: Parameter 6-54 Term 42 Output Timeout Preset
6-54 Term 42 Output Timeout Preset
Default value: 0%
Parameter type: Range, 0 - 100%
Setup: 1 setup
Conversion index: -2
Data type: Uint16
Change during operation: True
Holds the preset level of output 42. If a timeout function is selected in
parameter 6-50 Terminal 42 Output
, the output is preset to this
level if a fieldbus timeout occurs.
Parameter 6-55 Analog Output Filter
Table 429: Parameter 6-55 Analog Output Filter
6-55 Analog Output Filter
Default value: [0] Off
Parameter type: Option
Setup: 1 setup
Conversion index: –
Data type: Uint8
Change during operation: True
The following readout parameters from selection in
parameter 6-50 Terminal 42 Output
have a filter selected when
parameter 6-55
Analog Output Filter
is on.
Table 430: Readout Parameters
Selection
0–20 mA
4–20 mA
Motor current (I
max
)
[103]
[133]
Torque limit (0–T
lim
)
[104]
[134]
Rated torque (0–T
nom
)
[105]
[135]
Power (0–P
nom)
[106]
[136]
Speed (0–Speed
max
)
[107]
[137]
Option
Name
Description
[0]*
Off
Filter off.
[1]
On
Filter on.
5.7.7 6-6* Analog Output 2 MCB 101
Analog outputs are current outputs: 0/4–20 mA. Common terminal (terminal X30/8) is the same terminal and electrical potential for
analog common communication. Resolution on analog output is 12 bit.
AU275636650261en-000101 / 130R0334
242 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302