Parameter 36-53 Terminal X49/9 Max. Scale
Table 1339: Parameter 36-53 Terminal X49/9 Max. Scale
36-53 Terminal X49/9 Max. Scale
Default value: 100%
Parameter type: Range, 0 - 200%
Setup: All setups
Conversion index: 0
Data type: Int16
Change during operation: True
Scale the maximum output of terminal X49/9. For example, the scaling is done for the following reasons:
To provide an output value lower than the maximum possible value.
To provide the full signal range using output values lower than a certain limit.
To know more about how this parameter works, see
parameter 6-52 Terminal 42 Output Max Scale
.
Example:
Parameter 36-04 Terminal X49/9 Mode
=
[0] Voltage 0–10 V
Parameter 36-50 Terminal X49/9 Analogue Output
=
[100] Output Frequency
.
Parameter 4-19 Max Output Frequency
= 200 Hz.
Example case 1:
5 V maximum output is required when the output frequency is 200 Hz.
Parameter 36-53 Terminal X49/9 Max. Scale
x
100% = 200%.
Example case 2:
10 V maximum output is required when the output frequency is 150 Hz (75% of the maximum out-
put frequency).
Parameter 36-53 Terminal X49/9 Max. Scale
= 75%.
Parameter 36-54 Terminal X49/9 Bus Ctrl
Table 1340: Parameter 36-54 Terminal X49/9 Bus Ctrl
36-54 Terminal X49/9 Bus Ctrl
Default value: 0%
Parameter type: Range, 0 - 100%
Setup: All setups
Conversion index: 0
Data type: N2
Change during operation: True
This parameter contains the output level of terminal X49/9 if the terminal is controlled by bus.
Parameter 36-55 Terminal X49/9 Timeout Preset
Table 1341: Parameter 36-55 Terminal X49/9 Timeout Preset
36-55 Terminal X49/9 Timeout Preset
Default value: 0%
Parameter type: Range, 0 - 100%
Setup: 1 setup
Conversion index: 0
Data type: Uint16
Change during operation: True
The drive sends the value of this parameter to the output terminal when the terminal is controlled by a fieldbus and a timeout is
detected.
5.29.7 36-6* Output X49/11
Use the parameters in this group to configure the mode of inputs and outputs of VLT® Programmable I/O MCB 115.
N O T I C E
The following parameter is only available in FC 302:
Parameter 36-61 Terminal X49/11 Digital Output
.
Parameter 36-60 Terminal X49/11 Analogue Output
Table 1342: Parameter 36-60 Terminal X49/11 Analogue Output
36-60 Terminal X49/11 Analogue Output
Default value: [0] No operation
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True