Option
Name
Description
[3]
PT1000 2-wire
[5]
PT100 3-wire
[7]
PT1000 3-wire
Parameter 35-04 Term. X48/10 Temperature Unit
Table 1283: Parameter 35-04 Term. X48/10 Temperature Unit
35-04 Term. X48/10 Temperature Unit
Default value: [60] °C
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
Select the unit to be used with temperature input X48/10 settings and readouts.
Option
Name
Description
[60]*
°C
[160]
°F
Parameter 35-05 Term. X48/10 Input Type
Table 1284: Parameter 35-05 Term. X48/10 Input Type
35-05 Term. X48/10 Input Type
Default value: [0] Not connected
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
View the temperature sensor type detected at input X48/10.
Option
Name
Description
[0]*
Not connected
[1]
PT100 2-wire
[3]
PT1000 2-wire
[5]
PT100 3-wire
[7]
PT1000 3-wire
Parameter 35-06 Temperature Sensor Alarm Function
Table 1285: Parameter 35-06 Temperature Sensor Alarm Function
35-06 Temperature Sensor Alarm Function
Default value: [5] Stop and trip
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
Set the alarm function.
AU275636650261en-000101 / 130R0334
632 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide