Enter the tolerance window for on-reference or on-target status. Depending on the option selected in
parameter 1-00 Configuration
Mode
, this parameter defines the following:
Speed mode: Speed window for on-reference status.
Torque mode: Torque window for on-reference status.
Position mode: Speed window for on-target status. See also
parameter 3-08 On Target Window
.
Parameter 3-06 Minimum Position
Table 189: Parameter 3-06 Minimum Position
3-06 Minimum Position
Default value: -100000 Custom- Readout-
Unit2
Parameter type: Range, -2147483648 -
2147483647 CustomReadoutUnit2
Setup: All setups
Conversion index: 0
Data type: Int32
Change during operation: True
N O T I C E
This parameter is only available with software version 48.XX
Enter the minimum position. This parameter defines the position range in linear axis mode (
parameter 17-76 Position Axis Mode
) and
in the position limit function (
parameter 4-73 Position Limit Function
).
Parameter 3-07 Maximum Position
Table 190: Parameter 3-07 Maximum Position
3-07 Maximum Position
Default value: 100000 Custom- ReadoutU-
nit2
Parameter type: Range, -2147483648 -
2147483647 CustomReadoutUnit2
Setup: All setups
Conversion index: 0
Data type: Int32
Change during operation: True
N O T I C E
This parameter is only available with software version 48.XX
Enter the maximum position. This parameter defines the position range in linear axis mode (
parameter 17-76 Position Axis Mode
).
Position range limits:
Linear:
Parameter 3-06 Minimum Position
to
parameter 3-07 Maximum Position
.
Rotary: 0–
parameter 3-07 Maximum Position
.
The position limit function uses this parameter (
parameter 4-73 Position Limit Function
).
Parameter 3-08 On Target Window
Table 191: Parameter 3-08 On Target Window
3-08 On Target Window
Default value: 5 Custom- ReadoutUni t2 Parameter type: Range, 0 - 2147483647 CustomRea-
doutUnit2
Setup: All setups
Conversion index: 0
Data type: Int32
Change during operation: True
N O T I C E
This parameter is only available with software version 48.XX
The drive considers the positioning completed and sends the on target signal when the actual position is within
parameter 3-08 On
Target Window
for the duration of
parameter 3-09 On Target Time
and the actual speed is less than
parameter 3-05 On Reference Win-
dow
.