Parameter 10-13 Warning Parameter
Table 588: Parameter 10-13 Warning Parameter
10-13 Warning Parameter
Default value: 0
Parameter type: Range, 0 - 65535
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
View a DeviceNet-specific warning word. One bit is assigned to every warning. Refer to the VLT® DeviceNet MCA 104 Installation
Guide for further information.
Table 589: Warning Bits
Bit
Description
0
Bus not active
1
Explicit connection timeout
2
I/O connection
3
Retry limit reached
4
Actual is not updated
5
CAN bus off
6
I/O send error
7
Initialization error
8
No bus supply
9
Bus off
10
Error passive
11
Error warning
12
Duplicate MAC ID error
13
RX queue overrun
14
TX queue overrun
15
CAN overrun
Parameter 10-14 Net Reference
Table 590: Parameter 10-14 Net Reference
10-14 Net Reference
Default value: [0] Off
Parameter type: Option
Setup: 2 setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the reference source in instances 21/71 and 20/70.
Option
Name
Description
[0]*
Off
[1]
On
AU275636650261en-000101 / 130R0334 | 337
Danfoss A/S © 2022.12
Parameter Descriptions