Parameter 40-52 Speed PID Anti Windup Gain
Table 1365: Parameter 40-52 Speed PID Anti Windup Gain
40-52 Speed PID Anti Windup Gain
Default value: Size related
Parameter type: Range, 0 - 500%
Setup: All setups
Conversion index: 0
Data type: Int16
Change during operation: True
This Flux parameter is active in the drive when the following parameters are set to 1 of the values listed here:
Parameter 1-00 Configuration Mode
[0] Speed open loop
or
[1] Speed closed loop
or
[4] Torque open loop
Parameter 1-01 Motor Control Principle
[2] Flux sensorless
or
[3] Flux w/motor feedback
Parameter 1-10 Motor Construction
[0] Asynchron
or
[1] PM, non-salient SPM
or
[2] PM, salient IPM
Parameter 40-53 Current PID Anti Windup Gain
Table 1366: Parameter 40-53 Current PID Anti Windup Gain
40-53 Current PID Anti Windup Gain
Default value: Size related
Parameter type: Range, 0 - 500%
Setup: All setups
Conversion index: 0
Data type: Int16
Change during operation: True
This Flux parameter is active in the drive when the following parameters are set to 1 of the values listed here:
Parameter 1-00 Configuration Mode
[0] Speed open loop
or
[1] Speed closed loop
or
[4] Torque open loop
Parameter 1-01 Motor Control Principle
[2] Flux sensorless
or
[3] Flux w/motor feedback
Parameter 1-10 Motor Construction
[0] Asynchron
or
[1] PM, non-salient SPM
or
[2] PM, salient IPM
Parameter 40-54 Flux /w Feedback Dynamic Mode
Table 1367: Parameter 40-54 Flux /w Feedback Dynamic Mode
40-54 Flux /w Feedback Dynamic Mode
Default value: [0] Off
Parameter type: Option, array [2]
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: False
AU275636650261en-000101 / 130R0334
666 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide