Option Name
Description
[199]
RS Flipflop 7
See p
arameter group 13-1* Comparators
.
[221]
IGBT-cooling
Use this option for handling the overcurrent trips. When the drive detects an overcurrent condi-
tion, it shows
alarm 13, Overcurrent
and triggers a reset. If the overcurrent condition occurs 3
times in a row, the drive shows
alarm 13, Overcurrent
and initiates a 3 minute delay before the
next reset.
[222]
Homing OK
N O T I C E
This option is available only with software version 48.XX.
Homing is completed with the selected homing function (
parameter 17-80 Homing Function
).
[223]
On target
N O T I C E
This option is available only with software version 48.XX.
Positioning is completed and the on target signal is sent when the actual position is within
pa-
rameter 3-05 On Reference Window
for the duration of
parameter 3-09 On Target Time
and the
actual speed does not exceed
parameter 3-05 On Reference Window
.
[224]
Position limit
N O T I C E
This option is available only with software version 48.XX.
The position error exceeds the value in
parameter 4-71 Maximum Position Error
for the time set in
parameter 4-72 Position Error Timeout
.
[225]
Position error
N O T I C E
This option is available only with software version 48.XX.
The position is outside the limits set in
parameter 3-06 Minimum Position
and
parameter 3-07
Maximum Position
.
[226]
Touch on target
N O T I C E
This option is available only with software version 48.XX.
Target position is reached in touch probe position mode.
[227]
Touch activated
N O T I C E
This option is available only with software version 48.XX.
Touch probe positioning active. The drive monitors the touch probe sensor input.
[228]
Touch sensor found
N O T I C E
This option is available only with software version 48.XX.
The touch sensor has been detected.
AU275636650261en-000101 / 130R0334 | 215
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide