Option Name
Description
[224]
Position error
N O T I C E
This option is only available with software version 48.2X and newer.
The position error exceeds the value in
parameter 4-71 Maximum Position Error
for the time set
in
parameter 4-72 Position Error Timeout
.
[225]
Position limit
N O T I C E
This option is only available with software version 48.2X and newer.
The position is outside the limits set in
parameter 3-06 Minimum Position
and
parameter 3-07
Maximum Position
.
[226]
Touch on target
N O T I C E
This option is only available with software version 48.2X and newer.
Target position is reached in touch probe position mode.
[227]
Touch activated
N O T I C E
This option is only available with software version 48.2X and newer.
Touch probe positioning is active. The drive monitors the touch probe sensor input.
[249]
Therm. sensor temp.
Parameter 13-11 Comparator Operator
Table 675: Parameter 13-11 Comparator Operator
13-11 Comparator Operator
Default value: Size related
Parameter type: Option, Array [10]
Setup: 2 setups
Conversion index: -
Data type: Uint8
Change during operation: True
Select the operator to be used in the comparison. This is an array parameter containing comparator operators 0–5.
Op-
tion
Name
Description
[0]
<
N O T I C E
If
[20] Alarm number
or
[21] Warning number
is selected in
parameter 3-10 Comparator Operand
,
[0] <
cannot be selected in this parameter.
The result of the evaluation is true when the variable selected in
parameter 13-10 Comparator Operand
is smaller than the fixed value in
parameter 13-12 Comparator Value
. The result is false if the variable
selected in
parameter 13-10 Comparator Operand
is greater than the fixed value in
parameter 13-12
Comparator Value
.
[1]
≂
(equal)
The result of the evaluation is true when the variable selected in
parameter 13-10 Comparator Operand
is approximately equal to the fixed value in
parameter 13-12 Comparator Value
.
AU275636650261en-000101 / 130R0334 | 387
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide